Overview
© Schneider Electric 2011
17
1.9.1 Transmitting Error Reporting into OPC Alarms and Events error data
The conversion of Error Reporting messages to OPC Alarms and Events
error conditions involves the C-Bus network, C-Gate, OPC Server, and the
OPC Client as shown in the graphic below. The C-Bus OPC Server passes
Error Reporting messages retrieved from the C-Bus network to the C-Bus
OPC Server. The C-Bus OPC Server houses the OPC Alarms and Events
state machine which manages the error condition states of all Error
Reporting ready C-Bus units.
Figure 10: Component view of the OPC Alarms and Events implementation
C-Bus Network
C-Gate Server
OPC Server
Error
reporting
application
messages
Error reporting
application
message data
extraction
OPC Client
OPC event/
alarm
messages
Alarm
acknowledgements
State 1
State 2
State n
State machine
Error reporting conditions for the output unit
Below is a set of tables containing the OPC error conditions for each unit
type. Each table cross references the OPC error conditions against the
Error Reporting messages stored in C-Gate: