OPTION DESCRIPTION
DEFAULT YOUR SETTING
P150E 1E C-BUS ENABLE OFF
P75E 15E C-BUS FAILURE DIALLER REPORT OFF
P167E C-BUS ARM APPLICATION ADDRESS 56
P168E C-BUS ARM AREA 1 GROUP ADDRESS 255 (disabled)
P169E C-BUS ARM AREA 2 GROUP ADDRESS 255 (disabled)
P170E C-BUS ARM AREA 1 & AREA 2 GROUP ADDRESS 255 (disabled)
P150E 1E
C-BUS ENABLE
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
OFF (disabled).
NOTES
C-Bus operates in normal operating mode
only. C-bus messages are disabled if the
5400/16CB is in User or Installer program
mode.
This option enables the 5400/16CB C-Bus option.
PROGRAMMING SEQUENCE:
Press P150E 1E to toggle the option ON or OFF.
OFF: C-Bus is disabled.
ON: C-Bus is enabled.
P75E 15E
C-BUS FAILURE DIALLER REPORT
PROGRAM MODE LEVEL
Installer, Remote by PC.
FACTORY DEFAULT
OFF (disabled).
NOTES
This option enables the reporting by dialler of a "C-Bus Failure" message. If messages between
the 5400/16CB and the C-Bus have stopped for any reason, the 5400/16CB will attempt to
reconnect and then report a "C-Bus Failure" message if reconnection fails.
Press P75E 15E to toggle the option ON or OFF.
OFF: C-Bus failure Dialler report is disabled.
ON: C-Bus failure Dialler report is enabled.