1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 37
C-Bus Clock
When referring to a C-Bus Clock, we refer to a pulse that establishes and
synchronises communications on a C-Bus network. Without a C-Bus clock
you will not be able to operate or program any C-Bus units.
Each C-Bus network can only have one C-Bus clock active. Although there
can only be one active C-Bus Clock on a network, more can be enabled to
offer some basic redundancy.
It is recommended that each C-Bus network has a maximum of 3 C-Bus
clocks enabled on it. An internal algorithm will decide which clock will be
active, and will then deactivate the remaining enabled clocks.
When enabling a C-Bus Clock, try to enable it in the centre of the C-Bus
network to avoid attenuation and distortion due to:
cable length
cable capacitance
general interference.
The C-Bus Clock is actually a 5 Vp-p pulse that is superimposed onto the
C-Bus DC Voltage. The C-Bus clock can only be viewed using an
oscilloscope. The figure below shows a C-Bus clock as viewed through an
oscilloscope.
Figure 28 - A C-Bus clock viewed using an oscilloscope