Vue de la page 91
C-Bus™ Basic Programming 1250SM0904R10/09
C-Bus™ Products Training Course 10/2009
86 © 2009 Schneider Electric. All Rights Reserved.
Readdressing C-Bus Units
Typically after scanning a C-Bus Network for the first time, you will notice
that the unit addresses in the database does not match the unit addresses
on the network.
Readdressing C-Bus units is used to align the unit addresses of C-Bus units
in the network and database. This is particularly important, as it is a
contributing factor that will allow the full database to be downloaded into the
network.
To transfer the database to the network, there are two parameters that must
be identical between the network and database:
the unit address
the unit type.
An identical network and database will ensure that the correct programming
information is downloaded to the correct unit on the C-Bus network.
There are two common methods used to align the unit addresses between
the network and database:
manually readdressing each C-Bus unit to match the database
automatically readdress to match by serial numbers.
Readdress To Match Database
To readdress the unit address of a C-Bus unit on the network to match the
database, follow the steps below:
1) Scan the C-Bus network.
2) Select a single C-Bus unit in the network.
3) Navigate to the Units on Network toolbar in the Programming window,
and click on the small arrow to the right hand side of the Readdress
button. This will display more buttons related to readdressing C-Bus
units. Click on the Readdress to Match Database button and the form
below will appear.
Figure 64 - Readdress Physical Unit form